  • ✓︎ Direct measurement up to 100 A – single- & three-phase, no external CTs required
  • ✓︎ RS485 Modbus RTU – ideal for Deye hybrid inverters
  • ✓︎ Bidirectional & Class 1 – precise measurement of grid draw and feed-in

Available immediately
Delivery time: 2 - 5 Workdays

129,00 €
incl. 0% VAT , plus shipping costs
Pay securely via:
PayPal
Amazon Pay
ApplePay
Google Pay
Mastercard
Visa
Klarna
Rechnung

Question about item

Ask us your question

Question about item

Ask us your question

Description

The Eastron SDM630-Modbus V2 is a compact DIN-rail energy meter for single- and three-phase power grids. With direct connection up to 100 A, an RS485 Modbus interface, and bidirectional measurement, it is particularly well suited as an external energy meter for hybrid inverter systems – for example in combination with Deye hybrid inverters for controlling self-consumption and grid feed-in.

Key Benefits for Your System

  • Direct measurement up to 100 A: Connection is made without external current transformers, saving on costs and installation effort.
  • Usable for single- and three-phase systems: Supports the 1P2W, 3P3W, and 3P4W grid systems, making it suitable for almost any installation.
  • RS485 Modbus RTU: The Modbus interface allows the meter to be integrated into inverter and energy management systems and read remotely.
  • Bidirectional measurement: Grid draw and feed-in of active and reactive energy are recorded separately – the basis for self-consumption optimization and zero feed-in.
  • High accuracy: Active energy is measured to Class 1 according to IEC 62053-21.

Precise Grid Measurement for Your Energy System

For a hybrid inverter to control feed-in to the public grid or optimize self-consumption, it requires an accurate measurement of grid exchange at the grid connection point. This is exactly the task performed by the SDM630-Modbus V2: it continuously records voltage, current, power, power factor, and imported and exported energy, and makes the values available via RS485. Mounting is space-saving on a 35 mm DIN rail, and configuration of the Modbus address, baud rate, and pulse outputs is done directly on the front panel. Two pulse outputs are also available for energy recording. This allows you to keep track of generation and consumption at all times, providing the basis for efficient, grid-friendly interaction between your components. [PLEASE CHECK: specific connection/configuration requirements depend on the respective inverter manual – not included in the datasheet.]

GENERAL DATA (Basic meter information)
Manufacturer Eastron
Model SDM630-Modbus V2
Device type DIN-rail energy meter
Grid systems Single-phase (1P2W), three-phase (3P3W / 3P4W)
Mounting 35 mm DIN rail
Connection type Direct measurement up to 100 A (no current transformers)
Accuracy class Active energy Class 1 (IEC 62053-21)
MEASUREMENT & CONNECTION VALUES (Voltage & current)
Basic current (Ib) 10 A
Maximum current (Imax) 100 A
Minimum current 5% of Ib
Starting current 0.4% of Ib
Voltage L-N 100 – 289 V AC (not for 3P3W)
Voltage L-L 173 – 500 V AC (three-phase only)
Voltage input 4-way terminal for 25 mm² flexible cable
MEASURED VALUES & RANGES (Recorded values)
Measured values Voltage, current, frequency, active/reactive/apparent power, power factor, THD, max. power/current demand
Energy measurement Bidirectional: imported & exported active and reactive energy
Active power 0 – 99,999 W
Reactive power 0 – 99,999 VAr
Apparent power 0 – 99,999 VA
Energy 0 – 999,999.99 kWh / kVArh
Harmonic distortion (THD) up to the 19th harmonic
ACCURACY (Measurement tolerances)
Active energy Class 1 (IEC 62053-21)
Voltage 0.5% of max. measuring range
Current 0.5% of rated value
Active power ±1% of max. measuring range
Reactive power ±2% of max. measuring range
Frequency 0.2% of mean frequency range
Power factor 1% of unity (0.01)
COMMUNICATION & OUTPUTS (Interfaces)
Interface RS485 (Modbus RTU)
Baud rate 2400 / 4800 / 9600 / 19200 / 38400 bps
Modbus address 001 – 247
Parity none (default) / even / odd
Stop bits 1 or 2
Pulse outputs 2 (passive); output 1 configurable, output 2 fixed at 400 imp/kWh
Pulse width 200 / 100 / 60 ms
ENVIRONMENT & DIMENSIONS (Operation & design)
Operating temperature -25 °C to +55 °C
Storage temperature -40 °C to +70 °C
Relative humidity 0 – 90%, non-condensing
Operating altitude up to 2000 m
Warm-up time 10 s
Vibration 10 – 50 Hz, IEC 60068-2-6, 2 g
Dimensions (W × H × D) 72 × 100 × 66 mm (4 module units)

Scope of Delivery

  • Eastron SDM630-V2
  • User manual

Benutzerhandbuch

Variations

All variations to this product.

Question about item

Ask us your question
Contact data
Question about item

Benutzerhandbuch

Benutzerhandbuch


Reviews

We look forward to your review
Write the first review for this item and help others make a purchase decision!

There are no reviews yet.

Eastron SDM630-M Smart Meter for Deye

Eastron SDM630-M Smart Meter for Deye

129,00 € *

All categories

Select a category!

Accessibility

For easier usability
This is a sample text. The sample text helps you to better recognize the effect of the settings.

Welcome!

Please login or register.
Login for registered customers

Comparelist

Add some products to compare.
Please add at least two items to the comparison list.

Wishlist

Your favorite products

Visibility :

Find

No results
results for:
Enter at least 2 letters

Headline

Eine Subline
static content
static content
start
Ende

Another Headline

Eine Subline
Body Content